2VAC5-585-2270. Backflow prevention device, carbonator.
A. If not provided with an air gap as specified under 2VAC5-585-2200, a dual check valve with an intermediate vent preceded by a screen of not less than 100 mesh to one inch (100 mesh to 25.4mm) shall be installed upstream from a carbonating device and downstream from any copper in the water supply line.P
B. A dual check valve attached to the carbonator need not be of the vented type if an air gap or vented backflow prevention device has been otherwise provided as specified under subsection A of this section.
Statutory Authority
§ 3.2-5121 of the Code of Virginia.
Historical Notes
Derived from Virginia Register Volume 24, Issue 2, eff. October 16, 2007; amended, Virginia Register Volume 32, Issue 22, eff. July 12, 2016; Volume 37, Issue 19, eff. June 24, 2021.