12VAC5-590-1140. Installation and testing of water mains.
A. Adequate supports and restraints shall be provided for all pipes.
B. A continuous and uniform bedding shall be provided in the trench for all buried pipe.
C. Stones and rocks found in the trench shall be removed to a depth of at least six inches below the bottom of the pipe and selected fill bedding provided.
D. Installed pipe shall be pressure-tested and meet allowable leakage as specified in accordance with AWWA Standards C600-17, C604-17, and C605-13, where applicable.
E. Any plastic or other nonmetallic pressurized pipe installed underground shall be provided with a material conductive of electricity or some other means of locating the buried pipe.