Virginia Administrative Code
Title 13. Housing
Agency 5. Department of Housing and Community Development
Chapter 63. Virginia Uniform Statewide Building Code
1/23/2020

13VAC5-63-220. Chapter 4 Special Detailed Requirements Based on Use and Occupancy.

A. Delete Section 403.4.5 of the IBC.

B. Change Section 407.4.1.1 of the IBC to read:

407.4.1.1 Special locking arrangement. Means of egress doors shall be permitted to contain locking devices restricting the means of egress in areas in which the clinical needs of the patients require restraint of movement, where all of the following conditions are met:

1. The locks release upon activation of the fire alarm system or the loss of power.

2. The building is equipped with an approved automatic sprinkler system in accordance with Section 903.3.1.1.

3. A manual release device is provided at a nursing station responsible for the area.

4. A key-operated switch or other manual device is provided adjacent to each door equipped with the locking device. Such switch or other device, when operated, shall result in direct interruption of power to the lock -- independent of the control system electronics.

5. All staff shall have keys or other means to unlock the switch or other device or each door provided with the locking device.

C. Add Section 407.11 to the IBC to read:

407.11 Emergency power systems. Emergency power shall be provided for medical life support equipment, operating, recovery, intensive care, emergency rooms, fire detection and alarm systems in any Group I-2 occupancy licensed by the Virginia Department of Health as a hospital, nursing home or hospice facility.

D. Add Section 408.2.1 to the IBC to read:

408.2.1 Short-term holding areas. Short-term holding areas shall be permitted to comply with Section 429.

E. Change Section 408.6 of the IBC to read:

408.6 Smoke barrier. Occupancies classified as Group I-3 shall have smoke barriers complying with Sections 408.8 and 709 to divide every story occupied by residents for sleeping, or any other story having an occupant load of 50 or more persons, into no fewer than two smoke compartments.

F. Change Section 408.9 of the IBC and add Sections 408.9.1 through 408.9.3 to the IBC to read:

408.9 Smoke control. Smoke control for each smoke compartment shall be in accordance with Sections 408.9.1 through 408.9.3.

Exception: Smoke compartments with operable windows or windows that are readily breakable.

408.9.1 Locations. An engineered smoke control system shall comply with Section 909 and shall be provided in the following locations:

1. Dormitory areas.

2. Celled areas.

3. General housing areas.

4. Intake areas.

5. Medical celled or medical dormitory areas.

6. Interior recreation areas.

408.9.2 Compliance. The engineered smoke control system shall provide and maintain a tenable environment in the area of origin and shall comply with all of the following:

1. Shall facilitate the timely evacuation and relocation of occupants from the area of origin.

2. Shall be independent of exhaust systems under Chapter 5 of the IMC.

3. Duration of operation in accordance with Section 909.4.6.

4. The pressurization method shall be permitted and shall provide a minimum of 24 air changes per hour of exhaust, and 20 air changes per hour of makeup, and shall comply with Section 909.6. If the pressurization method is not utilized, the exhaust method shall be provided and shall comply with Section 909.8.

408.9.3 Corridors. Egress corridors within smoke compartments shall be kept free and clear of smoke.

G. Add an exception to Section 414.2 of the IBC to read:

Exception: Higher education teaching and research laboratories shall be permitted to comply with Section 430.

H. Add Section 414.6.2 to the IBC to read:

414.6.2 Other regulations. The installation, repair, upgrade, and closure of underground and aboveground storage tanks subject to the Virginia State Water Control Board regulations 9VAC25-91 and 9VAC25-580 shall be governed by those regulations, which are hereby incorporated by reference to be an enforceable part of this code. Where differences occur between the provisions of this code and the incorporated provisions of the State Water Control Board regulations, the provisions of the State Water Control Board regulations shall apply. Provisions of the International Fire Code addressing closure of such tanks that are subject to the Virginia State Water Control Board regulations 9VAC25-91 and 9VAC25-580 shall not be applicable.

I. Add IBC Section 427 Manufactured Homes and Industrialized Buildings.

J. Add Section 427.1 to the IBC to read:

427.1 General. The provisions of this section shall apply to the installation or erection of manufactured homes subject to the Virginia Manufactured Home Safety Regulations (13VAC5-95) and industrialized buildings subject to the Virginia Industrialized Building Safety Regulations (13VAC5-91).

Note: Local building departments are also responsible for the enforcement of certain provisions of the Virginia Manufactured Home Safety Regulations (13VAC5-95) and the Virginia Industrialized Building Safety Regulations (13VAC5-91) as set out in those regulations.

K. Add Section 427.2 to the IBC to read:

427.2 Site work for manufactured homes. Footing design, basements, grading, drainage, decks, stoops, porches and utility connections shall comply with the provisions of this code applicable to Group R-5 occupancies. Additionally, all applicable provisions of Chapter 1 of this code, including but not limited to requirements for permits, inspections, certificates of occupancy and requiring compliance, are applicable to the installation and set-up of a manufactured home. Where the installation or erection of a manufactured home utilizes components that are to be concealed, the installer shall notify the building official that an inspection is necessary and assure that an inspection is performed and approved prior to concealment of such components, unless the building official has agreed to an alternative method of verification.

L. Add Section 427.2.1 to the IBC to read:

427.2.1 Relocated manufactured homes. Installation, set-up, and site work for relocated manufactured homes shall comply with the provisions of this code and shall include the option of using the manufacturer's installations instructions or the federal Model Manufactured Home Installation Standards (24 CFR Part 3285) for the technical requirements.

M. Add Section 427.2.2 to the IBC to read:

427.2.2 Alterations and repairs to manufactured homes. Alterations and repairs to manufactured homes shall either be in accordance with federal Manufactured Home Construction and Safety Standards (24 CFR Part 3280) or in accordance with the alteration and repair provisions this code.

N. Add Section 427.2.3 to the IBC to read:

427.2.3 Additions to manufactured homes. Additions to manufactured homes shall comply with this code and shall be structurally independent of the manufactured home, or when not structurally independent, shall be evaluated by an RDP to determine that the addition does not cause the manufactured home to become out of compliance with federal Manufactured Home Construction and Safety Standards (24 CFR Part 3280).

O. Add Section 427.3 to the IBC to read:

427.3 Wind load requirements for manufactured homes. Manufactured homes shall be anchored to withstand the wind loads established by the federal regulation for the area in which the manufactured home is installed. For the purpose of this code, Wind Zone II of the federal regulation shall include the cities of Chesapeake, Norfolk, Portsmouth, and Virginia Beach.

P. Add Section 427.4 to the IBC to read:

427.4 Skirting requirements for manufactured homes. As used in this section, "skirting" means a weather-resistant material used to enclose the space from the bottom of the manufactured home to grade. In accordance with § 36-99.8 of the Code of Virginia, manufactured homes installed or relocated shall have skirting installed within 60 days of occupancy of the home. Skirting materials shall be durable, suitable for exterior exposures and installed in accordance with the manufacturer's installation instructions. Skirting shall be secured as necessary to ensure stability, to minimize vibrations, to minimize susceptibility to wind damage and to compensate for possible frost heave. Each manufactured home shall have a minimum of one opening in the skirting providing access to any water supply or sewer drain connections under the home. Such openings shall be a minimum of 18 inches (457 mm) in any dimension and not less than three square feet (.28 m2) in area. The access panel or door shall not be fastened in a manner requiring the use of a special tool to open or remove the panel or door. On-site fabrication of the skirting by the owner or installer of the home shall be acceptable, provided that the material meets the requirements of this code. In addition, as a requirement of this code, skirting for the installation and set-up of a new manufactured home shall also comply with the requirements of 24 CFR Part 3285 – Model Manufactured Home Installation Standards.

Q. Add Section 427.5 to the IBC to read:

427.5 Site work for industrialized buildings. Site work for the erection and installation of an industrialized building shall comply with the manufacturer's installation instructions. To the extent that any aspect of the erection or installation of an industrialized building is not covered by the manufacturer's installation instructions, this code shall be applicable, including the use of the IRC for any construction work where the industrialized building would be classified as a Group R-5 building. In addition, all administrative requirements of this code for permits, inspections, and certificates of occupancy are also applicable. Further, the building official may require the submission of plans and specifications for details of items needed to comprise the finished building that are not included or specified in the manufacturer's instructions, including, but not limited to, footings, foundations, supporting structures, proper anchorage, and the completion of the plumbing, mechanical, and electrical systems. Where the installation or erection of an industrialized building utilizes components that are to be concealed, the installer shall notify the building official that an inspection is necessary and assure that an inspection is performed and approved prior to concealment of such components, unless the building official has agreed to an alternative method of verification.

Exception: Temporary family health care structures installed pursuant to § 15.2-2292.1 of the Code of Virginia shall not be required or permitted to be placed on a permanent foundation, but shall otherwise remain subject to all pertinent provisions of this section.

R. Add Section 427.6 to the IBC to read:

427.6 Relocated industrialized buildings; alterations and additions. Industrialized buildings constructed prior to January 1, 1972, shall be subject to Section 117 when relocated. Alterations and additions to any existing industrialized buildings shall be subject to pertinent provisions of this code. Building officials shall be permitted to require the submission of plans and specifications for the model to aid in the evaluation of the proposed alteration or addition. Such plans and specifications shall be permitted to be submitted in electronic or other available format acceptable to the building official.

S. Add Section 427.7 to the IBC to read:

427.7 Change of occupancy of industrialized buildings. Change of occupancy of industrialized buildings is regulated by the Virginia Industrialized Building Safety Regulations (13VAC5-91). When the industrialized building complies with those regulations for the new occupancy, the building official shall issue a new certificate of occupancy under the USBC.

T. Add IBC Section 428 Aboveground Liquid Fertilizer Tanks.

U. Add Sections 428.1 through 428.6 to the IBC to read:

428.1 General. This section shall apply to the construction of ALFSTs and shall supersede any conflicting requirements in other provisions of this code. ALFSTs shall also comply with any applicable nonconflicting requirements of this code.

428.1.1 When change of occupancy rules apply. A change of occupancy to use a tank as an ALFST occurs when there is a change in the use of a tank from storing liquids other than liquid fertilizers to a use of storing liquid fertilizer and when the type of liquid fertilizer being stored has a difference of at least 20% of the specific gravity or operating temperature, or both, or a significant change in the material's compatibility.

428.2 Standards. Newly constructed welded steel ALFSTs shall comply with API 650 and TFI RMIP, as applicable. Newly constructed ALFSTs constructed of materials other than welded steel shall be constructed in accordance with accepted engineering practice to prevent the discharge of liquid fertilizer and shall be constructed of materials that are resistant to corrosion, puncture or cracking. In addition, newly constructed ALFSTs constructed of materials other than welded steel shall comply with TFI RMIP, as applicable. For the purposes of this code, the use of TFI RMIP shall be construed as mandatory and any language in TFI RMIP, such as, but not limited to, the terms "should" or "may" which indicate that a provision is only a recommendation or a guideline shall be taken as a requirement. ALFSTs shall be placarded in accordance with NFPA 704.

Exception: Sections 4.1.4, 4.2.5, 5.1.2, 5.2.8, 5.3 and 8.1(d)(i) of TFI RMIP shall not be construed as mandatory.

428.3 Secondary containment. When ALFSTs are newly constructed and when there is a change of occupancy to use a tank as an ALFST, a secondary containment system designed and constructed to prevent any liquid fertilizer from reaching the surface water, groundwater or adjacent land before cleanup occurs shall be provided. The secondary containment system may include dikes, berms or retaining walls, curbing, diversion ponds, holding tanks, sumps, vaults, double-walled tanks, liners external to the tank, or other approved means and shall be capable of holding up to 110% of the capacity of the ALFST as certified by an RDP.

428.4 Repair, alteration and reconstruction of ALFSTs. Repair, alteration and reconstruction of ALFSTs shall comply with applicable provisions of API 653 and TFI RMIP.

428.5 Inspection. Applicable inspections as required by and in accordance with API 653 and TFI RMIP shall be performed for repairs and alterations to ALFSTS, the reconstruction of ALFSTs and when there is a change of occupancy to use a tank as an ALFST. When required by API 653 or TFI RMIP, such inspections shall occur prior to the use of the ALFST.

428.6 Abandoned ALFSTs. Abandoned ALFSTs shall comply with applicable provisions of Section 5704.2.13.2 of the IFC.

V. Add IBC Section 429 Short-term Holding Areas.

W. Add Section 429.1 to the IBC to read:

429.1 General. In all groups other than Group E, short-term holding areas shall be permitted to be classified as the main occupancy, provided all of the following are met:

1. Provisions are made for the release of all restrained or detained occupants of short-term holding areas at all times.

2. Aggregate area of short-term holding areas shall not occupy more than 10% of the building area of the story in which they are located and shall not exceed the tabular values for building area in Table 506.2, without building area increases.

3. Restrained or detained occupant load of each short-term holding area shall not exceed 20.

4. Aggregate restrained or detained occupant load in short-term holding areas per building shall not exceed 80.

5. Compliance with Sections 408.3.7, 408.3.8, 408.4, and 408.7, as would be applicable to I-3 occupancies.

6. Requirements of the main occupancy in which short-term holding areas are located shall be met.

7. Fire areas containing short-term holding areas shall be provided with a fire alarm system and automatic smoke detection system complying with Section 907.2.6.3, as would be applicable to I-3 occupancies.

8. Where each fire area containing short-term holding areas exceeds 12,000 square feet (1115 m2), such fire areas shall be provided with an automatic sprinkler system complying with Section 903.3.

9. Short-term holding areas shall be separated from other short-term holding areas and adjacent spaces by smoke partitions complying with Section 710.

X. Add IBC Section 430 Higher Education Laboratories.

Y. Add Sections 430.1 through 430.4 to the IBC to read:

430.1 Scope. Group B teaching and research laboratories in educational occupancies above the 12th grade complying with the requirements of this section shall be permitted to comply with Table 430.3, 430.4(1), or 430.4(2) without requiring classification as a Group H occupancy. Except as specified in this section, such laboratories shall comply with all applicable provisions of this code. In addition, as set out in Section 5001.7 of the SFPC, approval under this section is contingent upon operational requirements in the SFPC being complied with and maintained.

430.2 Application. The provisions of this section shall be applied as exceptions or additions to applicable requirements of this code.

430.3 Laboratory suite construction. Where laboratory suites are provided, they shall be constructed in accordance with this section. The number of laboratory suites and percentage of maximum allowable quantities of hazardous materials in laboratory suites shall be in accordance with Table 430.3.

430.3.1 Separation from adjacent areas. Laboratory suites shall be separated from other portions of the building in accordance with the most restrictive of either (i) Table 430.3 with fire barriers constructed in accordance with Section 707 and horizontal assemblies constructed in accordance with Section 711 or (ii) Section 508.4. Where individual laboratories within a laboratory suite are separated from each other, the separation shall consist of one-hour fire barriers.

Exception: Where an individual laboratory suite occupies more than one story, the fire resistance rating of intermediate floors contained within the laboratory suite shall comply with the requirements of this code.

430.3.2 Separation from other laboratory suites. Laboratory suites shall be separated from other laboratory suites in accordance with Table 430.3.

430.3.3 Floor assembly fire resistance. The floor assembly supporting the laboratory suite and the construction supporting the floor of the laboratory suite shall have a fire resistance rating of not less than two hours.

Exception: The floor assembly of the laboratory suite and the construction supporting the floor of the laboratory suite are allowed to be one-hour fire resistance rated in buildings of Types IIA, IIIA, and VA construction, provided that the building is three or fewer stories.

430.3.4 Maximum number. The maximum number of laboratory suites per floor shall be in accordance with Table 430.3. Where a building contains both laboratory suites complying with Section 430.3 and control areas complying with Section 414.2, the total number of laboratory suites and control areas shall not exceed the maximum number of laboratory suites in accordance with Table 430.3.

430.3.5 Standby or emergency power. Standby or emergency power shall be provided in accordance with Section 414.5.2 where laboratory suites are located above the sixth story above grade plane or located in a story below grade plane.

430.3.6 Ventilation. Ventilation shall be in accordance with the International Mechanical Code. The design and installation of ducts from chemical fume hoods shall be in accordance with NFPA 91.

430.3.7 Liquid tight floor. Portions of the laboratory suite where hazardous materials are present shall be provided with a liquid tight floor.

430.3.8 Automatic fire sprinkler systems. Buildings shall be equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1.

430.3.9 Automatic fire alarm and detection system. Laboratory suites shall be equipped throughout with an automatic fire detection system in accordance with Section 907.2. The building shall be equipped throughout with an automatic fire alarm system in accordance with Section 907.2.

430.3.10 Percentage of maximum allowable quantity in each laboratory suite. The percentage of maximum allowable quantities in each laboratory suite shall be in accordance with Table 430.3.

Table 430.3

Design and Number of Laboratory Suites Per Floor

Floor Level

Percentage of the Maximum Allowable Quantity per Lab Suitea

Number of Lab Suites per Floor

Fire-Resistance Rating for Fire Barriers in Hoursb

Above Grade Plane

21+

5

1

2

16‑20

25

1

2

11‑15

50

1

2

7‑10

50

2

2

4‑6

75

4

1

3

100

6

1

1‑2

100

8

1

Below Grade Plane

1

75

4

1

2

50

2

1

Lower than 2

Not Allowed

Not Allowed

Not Allowed

a. Percentage shall be of the maximum allowable quantity per control area shown in Tables 307.1(1) and 307.1(2), with all increases allowed in the notes to those tables.

b. Fire barriers shall include walls, floors, and ceilings necessary to provide separation from other portions of the building.

430.4 Teaching and research laboratories utilizing control areas. Group B teaching and research laboratories in educational occupancies above the 12th grade utilizing control areas are permitted to increase amounts of hazardous materials stipulated in Section 414.2 without the laboratories being classified as Group H. The percentage of maximum allowable quantities of hazardous materials per control area and the number of control areas permitted at each floor level within a building shall be permitted to comply with Table 430.4(1) in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or shall be permitted to comply with Table 430.4(2) in buildings not equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. In addition, as set out in Section 5001.7 of the SFPC, approval under this section is contingent upon operational requirements in the SFPC being complied with and maintained.

Table 430.4(1)

Design and Number of Control Areas in Buildings Equipped Throughout with an Automatic Sprinkler System in Accordance with Section 903.3.1.1 with Group B Teaching and Research Laboratories in Educational Occupancies above the 12th Grade

Floor Level

Percentage of the Maximum Allowable Quantity per Control Areaa

Number of Control Areas per Floor

Fire-Resistance Rating for Fire Barriers and Horizontal Assemblies in Hoursb

Above Grade Plane

Higher than 20

5

1

2

11-20

10

1

2

7-10

25

2

2

4-6

50

2

2

3

75

3

1

1-2

100

4

1

Below Grade Plane

1

75

3

1

2

50

2

1

Lower than 2

Not Allowed

Not Allowed

Not Allowed

a. Percentage shall be of the maximum allowable quantity per control area shown in Tables 307.1(1) and 307.1(2), with all increases allowed in the notes to those tables.

b. Separation shall include fire barriers and horizontal assemblies as necessary to provide separation from other portions of the building.

Table 430.4(2)

Design and Number of Control Areas in Buildings Not Equipped Throughout with an Automatic Sprinkler System in Accordance with Section 903.3.1.1 with Group B Teaching and Research Laboratories in Educational Occupancies above the 12th Grade

Floor Level

Percentage of the Maximum Allowable Quantity per Control Areaa

Number of Control Areas per Floor

Fire-Resistance Rating for Fire Barriers and Horizontal Assemblies in Hoursb

Above Grade Plane

Higher than 9

5

1

2

7-9

10

2

2

4-6

25

2

2

3

75

2

1

1-2

100

4

1

Below Grade Plane

1

75

3

1

2

50

2

1

Lower than 2

Not Allowed

Not Allowed

Not Allowed

a. Percentage shall be of the maximum allowable quantity per control area shown in Tables 307.1(1) and 307.1(2), with all increases allowed in the notes to those tables.

b. Separation shall include fire barriers and horizontal assemblies as necessary to provide separation from other portions of the building.

430.4.1 Separation requirements. Control areas shall be separated from each other and from other non-control areas by fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both.

430.4.2 Fire resistance rating requirements. The required fire-resistance rating for fire barriers shall be in accordance with Table 430.4(1) in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or in accordance with Table 430.4(2) in buildings not equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The floor assembly of the control area and the construction supporting the floor of the control area shall have a fire-resistance rating in accordance with Table 430.4(1) in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or in accordance with Table 430.4(2) in buildings not equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.

Exception: The floor assembly of the control area and the construction supporting the floor of the control area are allowed to be one-hour fire resistance rated in buildings of Types IIA, IIIA, and VA construction, provided that the building is three or fewer stories.

430.4.3 Standby or emergency power. Standby or emergency power shall be provided where control areas are located above the sixth floor level above grade plane or located in a floor level below grade plane.

430.4.4 Restricted materials in storage and use. Where approved by the building official, the storage and use of the following hazardous materials prohibited by Table 307.1(1) in buildings not equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, shall be allowed within a control area at 25% of Table 307.1(1) limits for a building equipped throughout with an automatic sprinkler system:

1. Pyrophorics.

2. Class 4 oxidizers.

No additional quantity increases shall be allowed. All such materials shall be stored and used in accordance with Section 5001.7 of the SFPC.

430.4.5 Automatic fire alarm and detection system. The building shall be equipped throughout with an automatic fire alarm system in accordance with Section 907.2, and control areas where hazardous materials are used or stored shall be equipped throughout with an automatic fire detection system in accordance with Section 907.2.

430.4.6 Ventilation. Ventilation shall be in accordance with the International Mechanical code.

Statutory Authority

§ 36-98 of the Code of Virginia.

Historical Notes

Derived from Volume 22, Issue 03, eff. November 16, 2005; amended, Virginia Register Volume 24, Issue 14, eff. May 1, 2008; Volume 25, Issue 17, eff. June 1, 2009; Volume 27, Issue 02, eff. March 1, 2011; Change in Effective Date, 27:5 VA.R. 534 November 8, 2010; amended, Virginia Register Volume 30, Issue 16, eff. July 14, 2014: Errata 30:24 VA.R. 2698 July 28, 2014; amended, Virginia Register Volume 34, Issue 18, eff. September 4, 2018.

Website addresses provided in the Virginia Administrative Code to documents incorporated by reference are for the reader's convenience only, may not necessarily be active or current, and should not be relied upon. To ensure the information incorporated by reference is accurate, the reader is encouraged to use the source document described in the regulation.

As a service to the public, the Virginia Administrative Code is provided online by the Virginia General Assembly. We are unable to answer legal questions or respond to requests for legal advice, including application of law to specific fact. To understand and protect your legal rights, you should consult an attorney.