19VAC30-70-680. Fuel system.
Inspect for and reject if:
1. Any part of the fuel system is not securely fastened.
2. There is fuel leakage at any point in any fuel system.
3. Any fuel tank filler cap is missing.
4. Any fuel tank crossover lines are not protected if they extend more than two inches below the bottom of the tank or sump.
5. Any part of the fuel system comes in contact with the exhaust system.
Statutory Authority
§ 46.2-1165 of the Code of Virginia.
Historical Notes
Derived from VR545-01-07 § 68, eff. May 1, 1990; amended, Virginia Register Volume 10, Issue 8, eff. February 9, 1994; Volume 15, Issue 2, eff. November 11, 1998.
Website addresses provided in the Virginia Administrative Code to documents incorporated by reference are for the reader's convenience only, may not necessarily be active or current, and should not be relied upon. To ensure the information incorporated by reference is accurate, the reader is encouraged to use the source document described in the regulation.
As a service to the public, the Virginia Administrative Code is provided online by the Virginia General Assembly. We are unable to answer legal questions or respond to requests for legal advice, including application of law to specific fact. To understand and protect your legal rights, you should consult an attorney.