6VAC15-81-980. Mechanical, plumbing, electrical, smoke control, and fire protection installation.
Unless indicated otherwise by this chapter, all components of mechanical, plumbing, electrical, smoke control, and fire protection systems, including air handlers, fans, duct work, terminal boxes, dampers, heating and cooling equipment, water heaters, pumps, piping, valves, sensors, control wiring, thermostats, tubing, conduit, wiring, motors, lighting fixtures, and associated equipment within the secure perimeter shall be mounted as follows:
1. As high as possible for the intended function and securely fastened to the structure or walls.
2. If located less than 12 feet above the finished floor or within six feet horizontally of guard rails enclosing tier floor and landing levels in dayrooms, the components shall be specifically designed for the security level of the space where it is installed, protected by a secure enclosure, or protected by secure encapsulation. Exceptions include spaces dedicated for staff use. "Secure enclosure" means secure walls, secure floors, and secure roof or secure ceiling surrounding a space or area.
3. Piping, wiring, conduit, control wiring, and tubing shall not be exposed in cells.