Chapter 75. General Industry Standard for Telecommunications, General, Approach Distances
16VAC25-75-10. General; approach distances.
A. No employee shall be permitted to approach or take any conductive object closer to exposed energized parts than shown in subsection B (Table R-2) of this section unless:
1. The employee is insulated or guarded from the energized parts (insulating gloves or insulating gloves and sleeves worn in accordance with 16VAC25-90-1910.269(l)(3) are only considered insulation of that part of the employee's extremities covered by the insulating gloves or insulating gloves and sleeves);
2. The energized part is insulated or guarded from him and any other conductive object at a different potential; or
3. The power conductors and equipment are deenergized and grounded.
B. Approach distances to exposed energized overhead power lines and parts.
TABLE R-2. | |
Voltage range | Approach distance (inches) |
300 V and less | (1) |
Over 300 V, not over 750V | 12 |
Over 750 V not over 2 kV | 18 |
Over 2 kV, not over 15 kV | 24 |
Over 15 kV, not over 37 kV | 36 |
Over 37 kV, not over 87.5 kV | 42 |
Over 87.5 kV, not over 121 kV | 48 |
Over 121 kV, not over 140kV | 54 |
(1) Avoid contact.
Statutory Authority
§ 40.1-22 of the Code of Virginia; Occupational Safety and Health Act of 1970 (P.L. 91-596).
Historical Notes
Derived from Virginia Register Volume 23, Issue 21, eff. July 26, 2007.