§ 45.2-912. Firefighting equipment; duties in case of fire; fire precaution in transportation of mining equipment; fire prevention generally.
A. Each mine shall be provided with suitable firefighting equipment that is adequate for the size of the mine and includes at least three 20-pound dry chemical fire extinguishers. Equipment and devices used for the detection, warning, and extinguishing of fires shall be suitable in type, size, and quantity for the type of fire hazard that could be encountered. Such equipment and devices shall be strategically located and plainly identified.
B. Suitable fire extinguishers shall be provided at or on each (i) electrical station, such as a substation, transformer station, or permanent pump station; (ii) piece of self-propelled mobile equipment; (iii) belt head; (iv) area used for the storage of flammable materials; (v) fueling station; and (vi) other area that could constitute a fire hazard. Such fire extinguishers shall be placed so as to be out of the smoke in case of a fire.