12VAC5-610-592. Setback distances.
A. Septic tanks, other tanks, and header line setback distances. The minimum separation distances between septic tanks, pump chambers, aerobic pretreatment devices (including sand filters, biofilters, and aerobic treatment units), header lines, and similar devices as determined by the department, and various structures and topographic features are contained in Table 4.1 entitled Minimum Separation Distances for Pretreatment Units, Conveyance Lines, and Header Lines.
B. Manifolds. Manifolds shall not pass closer than 50 feet to any drinking water source unless pressure tested in place at pump shut-off head. Under no circumstances shall a manifold come within 10 feet of a drinking water source.
C. Absorption area. The absorption area is the soil medium beginning at the interface between the soil and the gravel, sand, or other point of effluent application, which is utilized for dispersal of the effluent. The absorption area includes the infiltrative surface in the absorption trench, or the point of effluent application, and the soil between and around the effluent distribution system. Setback distance to various structures and topographic features and an absorption area are contained in Table 4.2.
Statutory Authority
§§ 32.1-12 and 32.1-164 of the Code of Virginia.
Historical Notes
Derived from Virginia Register Volume 16, Issue 16, eff. July 1, 2000.