13VAC5-51-140. Ifc Chapter 23 Motor Fuel-Dispensing Facilities and Repair Garages.

A. The following changes shall be made to Section 2301, General:

1. Change Section 2301.1 to read:

2301.1 Scope. The operation and maintenance of automotive motor fuel-dispensing facilities, marine motor fuel-dispensing facilities, fleet vehicle motor fuel-dispensing facilities, aircraft motorvehicle fuel-dispensing facilities, and repair garages shall be in accordance with this chapter. Such operations shall include both those that are accessible to the public and private operations.

2. Change Section 2301.2 to read:

2301.2 Permits. Permits shall be required as set forth in Section 107.2.

3. Delete Section 2301.3.

4. Change Section 2301.4 to read:

(N)2301.4 Indoor motor fuel-dispensing facilities. Motor fuel-dispensing facilities located inside buildings shall be maintained in accordance with NFPA 30A and the applicable building code.

5. Change Section 2301.5 to read:

(N)2301.5 Electrical. Electrical wiring and equipment shall be maintained in accordance with NFPA 30A and the applicable building code.

6. Change Section 2301.6 to read:

2301.6 Heat-producing appliances. Heat-producing appliances shall be suitable for the locations in which they are installed and shall comply with NFPA 30A.

B. The following changes shall be made to Section 2303, Location of Dispensing Devices:

1. Change Section 2303.1 to read:

(N)2303.1 Location of dispensing devices. Dispensing devices shall be maintained in accordance with the applicable building code.

2. Change Section 2303.2 to read:

(N)2303.2 Emergency disconnect switches. Emergency disconnect switches shall be maintained in accordance with the applicable building code.

C. The following changes shall be made to Section 2304, Dispensing Operations:

1. Change Section 2304.2.2 to read:

(N)2304.2.2 Emergency controls. Approved emergency controls shall be provided in accordance with the applicable building code.

2. Change Section 2304.3.2 to read:

(N)2304.3.2 Dispensers. Dispensing devices shall be maintained in accordance with the applicable building code.

3. Change Section 2304.3.3 to read:

2304.3.3 Emergency controls. Approved emergency controls shall be maintained in accordance with the applicable building code. Emergency controls shall be of a type that is only manually resettable.

4. Change Section 2304.3.5 to read:

2304.3.5 Emergency procedures. An approved emergency procedures sign, in addition to the signs required by Section 2305.6, shall be posted and maintained in a conspicuous location and shall read:

IN CASE OF FIRE SPILL OR RELEASE

1. USE EMERGENCY PUMP SHUTOFF

2. REPORT THE ACCIDENT!

FIRE DEPARTMENT TELEPHONE NO.________

FACILITY ADDRESS:_______________________

D. The following changes shall be made to Section 2305, Operational Requirements:

1. Change Section 2305.2.4 to read:

2305.2.4 Emergency shutoff valves. Automatic emergency shutoff valves shall be checked not less than once each year by manually tripping the hold-open linkage.

2. Change Section 2305.2.5 to read:

2305.2.5 Leak detectors. Leak detection devices shall be checked and tested not less than annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

3. Change Section 2305.4 to read:

2305.4 Sources of ignition. Smoking and open flames shall be prohibited within 20 feet (6096 mm) of a fuel dispensing device. The engines of vehicles being fueled shall be shut off during fueling. Electrical equipment shall be in accordance with NFPA 70.

E. The following changes shall be made to Section 2306, Flammable and Combustible Liquid Motor Fuel-Dispensing Facilities:

1. Change Section 2306.1 to read:

2306.1 General. Operation and maintenance of flammable and combustible liquid motor fuel-dispensing facilities shall be in accordance with Chapter 57 and Sections 2306.2 through 2306.6.3 and other applicable provisions of this code.

2. Change Section 2306.2.1.1 to read:

2306.2.1.1 Inventory control and leak detection for underground tanks. Accurate inventory records shall be maintained on underground fuel storage tanks for indication of possible leakage from tanks and piping. The records shall be kept at the premises or made available for inspection by the fire official within 24 hours of a written or verbal request and shall include records for each tank. Where there is more than one system consisting of tanks serving separate pumps or dispensers for a product, the inventory record shall be maintained separately for each tank system.

Owners and operators of underground fuel storage tanks shall provide release detection for tanks and piping that routinely contain flammable and combustible liquids in accordance with one of the following methods:

1. Monthly inventory control to detect a release of at least 1.0% of flow-through plus 130 gallons.

2. Manual tank gauging for tanks with 2,000 gallon capacity or less when measurements are taken at the beginning and ending of a 36-hour to 58-hour period during which no liquid is added to or removed from the tank.

3. Tank tightness testing capable of detecting a 0.1 gallon per hour leak rate.

4. Automatic tank gauging that tests for loss of liquid.

5. Vapor monitoring for vapors within the soil of the tank field.

6. Groundwater monitoring when the groundwater is never more than 20 feet from the ground surface.

7. Interstitial monitoring between the underground tank and a secondary barrier immediately around or beneath the tank.

8. Other approved methods that have been demonstrated to be as effective in detecting a leak as the methods listed above.

A consistent or accidental loss of product shall be immediately reported to the fire official.

3. Change Section 2306.2.2 to read:

(N)2306.2.2 Aboveground tanks located inside buildings. Aboveground tanks for the storage of Classes I, II and IIIA liquid fuels located in buildings shall be maintained in accordance with the applicable building code.

4. Change Section 2306.2.3 to read:

(N)2306.2.3 Aboveground tanks located outside above grade. Aboveground tanks located outside shall be maintained in accordance with the applicable building code.

5. Delete Table 2306.2.3.

6. Change Section 2306.2.4 to read:

(N)2306.2.4 Aboveground tanks located in above-grade vaults or below-grade vaults. Aboveground tanks located in above-grade vaults or below-grade vaults shall be maintained in accordance with the applicable building code.

7. Delete Section 2306.2.4.1.

8. Change Section 2306.2.4.2 to read:

(N)2306.2.4.2 Fleet vehicle motor fuel-dispensing facilities. Tanks storing liquids at a fleet vehicle motor fuel-dispensing facility shall be maintained in accordance with the applicable building code.

9. Change Section 2306.2.6 to read:

(N)2306.2.6 Special enclosures. Special enclosures shall be maintained in accordance with the applicable building code.

10. Change Section 2306.5 to read:

(N)2306.5 Secondary containment. Aboveground tanks provided with drainage control or diking shall be maintained in accordance with Chapter 57 and the applicable building code.

11. Change Section 2306.6 to read:

(N)2306.6 Piping, valves, fittings and ancillary equipment for use with flammable or combustible liquids. The design, fabrication, assembly, testing and inspection of piping, valves, fittings and ancillary equipment for use with flammable or combustible liquids shall be maintained in accordance with the applicable building code.

12. Change Section 2306.6.2 to read:

(N)2306.6.2 Piping, valves, fittings and ancillary equipment for aboveground tanks for Classes I, II and III liquids. Piping, valves, fittings and ancillary equipment for aboveground tanks shall be maintained in accordance with the applicable building code.

13. Delete Section 2306.6.2.1.

14. Change Section 2306.6.2.2 to read:

(N)2306.6.2.2 Fill-pipe connections. The fill pipe for aboveground tanks shall be maintained in accordance with the applicable building code.

15. Change Section 2306.6.2.3 to read:

(N)2306.6.2.3 Overfill protection. Overfill protection shall be in accordance with the applicable building code.

16. Change Section 2306.6.2.4 to read:

(N)2306.6.2.4 Siphon prevention. An approved antisiphon method shall be maintained in accordance with the applicable building code.

17. Change Section 2306.6.2.5 to read:

(N)2306.6.2.5 Emergency relief venting. Aboveground storage tanks, tank compartments, and enclosed secondary containment spaces shall be maintained in accordance with the applicable building code.

18. Change Section 2306.6.2.6 to read:

(N)2306.6.2.6 Spill containers. Spill containers shall be maintained in accordance with the applicable building code.

19. Change Section 2306.6.3 to read:

(N)2306.6.3 Piping, valves, fittings and ancillary equipment for underground tanks. Piping, valves, fittings and ancillary equipment for underground tanks shall be maintained in accordance with the applicable building code.

20. Change Section 2306.7 to read:

(N)2306.7 Fuel-dispensing systems for flammable or combustible liquids. Fuel-dispensing systems for flammable or combustible liquid fuels shall be maintained in accordance with the applicable building code.

21. Delete Section 2306.7.1.

22. Delete Section 2306.7.2.

23. Change Section 2306.7.3 to read:

(N)2306.7.3 Mounting of dispensers. Dispensing devices, except those installed on top of a protected aboveground tank that qualifies as vehicle-impact resistant, shall be maintained in accordance with the applicable building code.

24. Change Section 2306.7.4 to read:

(N)2306.7.4 Dispenser emergency shutoff valve. Dispenser emergency shutoff valves shall be maintained in accordance with the applicable building code.

25. Change Section 2306.7.5 to read:

(N)2306.7.5 Dispenser hose. Dispenser hoses shall be maintained in accordance with the applicable building code.

26. Change Section 2306.7.5.1 to read:

(N)2306.7.5.1 Emergency breakaway devices. Emergency breakaway devices shall be maintained in accordance with the applicable building code.

27. Change Section 2306.7.6 to read:

(N)2306.7.6 Fuel delivery nozzles. Fuel delivery nozzles shall be maintained in accordance with the applicable building code.

28. Delete Section 2306.7.6.1.

29. Change Section 2306.7.7 to read:

(N)2306.7.7 Remote pumping systems. Remote pumping systems for liquid fuels shall be maintained in accordance with the applicable building code.

30. Change Section 2306.7.7.1 to read:

(N)2306.7.7.1 Leak detection. Leak detection devices shall be maintained in accordance with the applicable building code.

31. Delete Section 2306.7.7.2.

32. Change Section 2306.7.9 to read:

(N)2306.7.9 Vapor-recovery and vapor-processing systems. Vapor-recovery and vapor-processing systems shall be maintained in accordance with the applicable building code.

33. Change Section 2306.7.9.1 to read:

(N)2306.7.9.1 Vapor-balance systems. Vapor-balance systems shall be maintained in accordance with the applicable building code.

34. Change Section 2306.7.9.1.1 to read:

(N)2306.7.9.1.1 Dispensing devices. Dispensing devices shall be maintained in accordance with the applicable building code.

35. Change Section 2306.7.9.1.2 to read:

(N)2306.7.9.1.2 Vapor-return line closeoff. Vapor-return line closeoffs shall be maintained in accordance with the applicable building code.

36. Change Section 2306.7.9.1.3 to read:

(N)2306.7.9.1.3 Piping. Piping in vapor-balance systems shall be maintained in accordance with the applicable building code.

37. Change Section 2306.7.9.1.4 to read:

(N)2306.7.9.1.4 Flexible joints and shear joints. Flexible joints and shear joints shall be maintained in accordance with the applicable building code.

38. Delete Section 2306.7.9.1.5.

39. Change Section 2306.7.9.2 to read:

(N)2306.7.9.2 Vapor-processing systems. Vapor-processing systems shall be maintained in accordance with the applicable building code.

40. Change Section 2306.7.9.2.1 to read:

(N)2306.7.9.2.1 Equipment. Equipment in vapor-processing systems, including hose nozzle valves, vapor pumps, flame arresters, fire checks or systems for prevention of flame propagation, controls, and vapor-processing equipment, shall be maintained in accordance with the applicable building code.

41. Delete Section 2306.7.9.2.2.

42. Delete Section 2306.7.9.2.2.1.

43. Change Section 2306.7.9.2.2.2 to read:

(N)2306.7.9.2.2.2 Physical protection. Physical protection for vapor-processing equipment shall be maintained in accordance with the applicable building code.

44. Delete Section 2306.7.9.2.2.3.

45. Delete Section 2306.7.9.2.3.

46. Change Section 2306.7.9.2.4 to read:

(N)2306.7.9.2.4 Piping. Piping in a mechanical-assist system shall be maintained in accordance with the applicable building code.

47. Change Section 2306.8 to read:

(N)2306.8 Alcohol-blended fuel-dispensing operations. Alcohol-blended fuel-dispensing systems shall be maintained in accordance with the applicable building code.

48. Delete Section 2306.8.2.

49. Delete Section 2306.8.3.

50. Delete Section 2306.8.4.

F. The following changes shall be made to Section 2307, Liquefied Petroleum Gas Motor Fuel-Dispensing Facilities:

1. Change Section 2307.1 to read:

(N)2307.1 General. Operation and maintenance of motor fuel-dispensing facilities for liquefied petroleum gas (LP-gas) fuel shall be in accordance with this section and other applicable provisions of this code.

2. Delete Section 2307.2.

3. Delete Section 2307.2.1.

4. Delete Section 2307.2.2.

5. Change Section 2307.3 to read:

2307.3 Attendants. Motor fuel-dispensing operations for LP-gas shall be conducted by qualified attendants or by persons trained in the proper handling of LP-gas.

6. Change Section 2307.4 to read:

(N)2307.4 Location of dispensing operations and equipment. LP-gas containers shall be located in accordance with the applicable building code.

7. Delete Section 2307.5.

8. Delete Section 2307.6.

9. Delete Section 2307.6.1.

10. Change Section 2307.6.2 to read:

(N)2307.6.2 Hoses. Hoses and piping for the dispensing of LP-gas shall be maintained in accordance with the applicable building code.

11. Delete Section 2307.6.3.

12. Change Section 2307.7 to read:

(N)2307.7 Public fueling of motor vehicles. Self-service LP-gas dispensing systems, including key, code, and card lock dispensing systems, shall be limited to the filling of permanently mounted containers providing fuel to the LP-gas powered vehicle.

The requirements for self-service LP-gas dispensing systems shall be in accordance with the following:

1. The arrangement and operation of the transfer of product into a vehicle shall be in accordance with this section and Chapter 61.

2. The owner of the LP-gas motor fuel-dispensing facility or the owner's designee shall provide for the safe operation of the system and the training of users.

3. Portable fire extinguishers shall be provided in accordance with Section 2305.5.

4. Warning signs shall be provided in accordance with Section 2305.6.

5. The area around the dispenser shall be maintained in accordance with Section 2305.7.

G. The following changes shall be made to Section 2308, Compressed Natural Gas Motor Fuel-Dispensing Facilities:

1. Change Section 2308.1 to read:

2308.1 General. Motor fuel-dispensing facilities for compressed natural gas (CNG) fuel shall be maintained in accordance with the applicable building code.

2. Change Section 2308.2.2 to read:

(N)2308.2.2 Listed equipment. Hoses, hose connections, dispensers, gas detection systems, and electrical equipment used for CNG shall be listed. Vehicle-fueling connections shall be listed and labeled and maintained in accordance with the applicable building code.

3. Delete Section 2308.3.

4. Delete Section 2308.3.1.

5. Change Section 2308.5 to read:

(N)2308.5 Pressure regulators. Pressure regulators shall be maintained in accordance with the applicable building code.

6. Change Section 2308.6 to read:

(N)2308.6 Valves. Gas piping to equipment shutoff valves shall be maintained in accordance with the applicable building code.

7. Change Section 2308.7 to read:

(N)2308.7 Emergency shutdown control. Emergency shutdown controls shall be maintained in accordance with the applicable building code.

H. The following changes shall be made to Section 2309, Hydrogen Motor Fuel-Dispensing and Generation Facilities:

1. Change Section 2309.1 to read:

2309.1 General. Operation and maintenance of hydrogen motor fuel-dispensing and generation facilities shall be in accordance with this section and other applicable provisions of this code. Where a fuel-dispensing facility includes a repair garage, the repair operation shall comply with Section 2311.

2. Change Section 2309.2 to read:

(N)2309.2 Equipment. Equipment used for the generation, compression, storage, or dispensing of hydrogen shall be maintained in accordance with the applicable building code.

3. Change Section 2309.2.1 to read:

(N)2309.2.1 Approved equipment. Cylinders, containers, and tanks; pressure relief devices, including pressure valves; hydrogen vaporizers; pressure regulators; and piping used for gaseous hydrogen systems shall be maintained in accordance with the applicable building code.

4. Change Section 2309.2.2 to read:

(N)2309.2.2 Listed or approved equipment. Hoses, hose connections, compressors, hydrogen generators, dispensers, detection systems, and electrical equipment used for hydrogen shall be listed or approved for use with hydrogen and maintained in accordance with the applicable building code.

5. Change Section 2309.2.3 to read:

(N)2309.2.3 Electrical equipment. Electrical installations shall be maintained in accordance with the applicable building code.

6. Change Section 2309.3 to read:

(N)2309.3 Location on property. Location of dispensing equipment shall be maintained in accordance with the applicable building code.

7. Change Section 2309.1.1. to read:

(N)2309.3.1.1 Outdoors. Generation, compression, or storage equipment shall be maintained in accordance with the applicable building code.

8. Change Section 2309.3.1.2 to read:

(N)2309.3.1.2 Indoors. Generation, compression, storage and dispensing equipment shall be maintained in accordance with the applicable building code.

9. Change Section 2309.3.1.3 to read:

(N)2309.3.1.3 Gaseous hydrogen storage. Storage of gaseous hydrogen shall be maintained in accordance with the applicable building code.

10. Change Section 2309.3.1.4 to read:

(N)2309.3.1.4 Liquefied hydrogen storage. Storage of liquefied hydrogen shall be maintained in accordance with the applicable building code.

11. Change Section 2309.3.1.5 to read:

(N)2309.3.1.5 Canopy tops. Gaseous hydrogen compression and storage equipment located on top of motor fuel-dispensing facility canopies shall be maintained in accordance with the applicable building code.

12. Delete Section 2309.3.1.5.1.

13. Change Section 2309.3.1.5.2 to read:

(N)2309.3.1.5.2 Fire-extinguishing systems. Fire-extinguishing provided for fuel-dispensing areas under canopies shall be maintained in accordance with the applicable building code.

14. Delete Section 2309.3.1.5.3.

15. Delete Section 2309.3.1.5.4.

16. Delete Section 2309.3.2.

17. Change Section 2309.4.1 to read:

(N)2309.4.1 Dispensing systems. Dispensing systems shall be maintained in accordance with the applicable building code.

18. Change Section 2309.5 to read:

(N)2309.5 Safety precautions. Safety precautions at hydrogen motor fuel-dispensing and generation facilities shall be in accordance with Sections 2309.5.1 through 2309.5.3.

19. Change Section 2309.5.2 to read:

(N)2309.5.2 Emergency shutoff valves. Manual emergency shutoff valves shall be maintained in accordance with the applicable building code.

20. Change Section 2309.5.3 to read:

(N)2309.5.3 Emergency shutdown controls. Emergency shutdown controls shall be maintained in accordance with the applicable building code.

21. Delete Section 2309.5.3.1.

22. Change Section 2309.6.1.2.1.2 to read:

(N)2309.6.1.2.1.2 Vent pipe maximum diameter. Vent pipe diameter shall be maintained in accordance with the applicable building code.

23. Change Section 2309.6.1.2.1.3 to read:

(N)2309.6.1.2.1.3 Maximum flow rate. The maximum rate of hydrogen flow through the vent pipe system shall be maintained in accordance with the applicable building code.

24. Delete Section 2309.6.1.2.2.

25. Delete Section 2309.6.1.2.3.

26. Change Section 2309.6.1.2.4 to read:

(N)2309.6.1.2.4 Grounding and bonding. Grounding and bonding of cylinders, containers or tanks, and piping shall be maintained in accordance with the applicable building code.

27. Change Section 2309.6.2 to read:

(N)2309.6.2 Repair of hydrogen piping. Piping systems containing hydrogen shall not be opened to the atmosphere for repair without first purging the piping with an inert gas to achieve 1% hydrogen or less by volume.

I. The following changes shall be made to Section 2310, Marine Motor Fuel-Dispensing Facilities:

1. Change Section 2310.1 to read:

2310.1 General. The construction of marine motor fuel-dispensing facilities shall be in accordance with this section and other applicable provisions of this code.

2. Change Section 2310.2 to read:

(N)2310.2 Storage and handling. The storage and handling of Class I, II or IIIA liquids at marine motor fuel-dispensing facilities shall be maintained in accordance with the applicable building code.

3. Change Section 2310.2.1 to read:

(N)2310.2.1 Class I, II or IIIA liquid storage. Class I, II or IIIA liquids stored inside of buildings used for marine motor fuel-dispensing facilities shall be stored in accordance with the applicable building code.

4. Change Section 2310.2.2 to read:

(N)2310.2.2 Class II or IIIA liquid storage and dispensing. Class II or IIIA liquids stored or dispensed inside of buildings used for marine motor fuel-dispensing facilities shall be stored in and dispensed in accordance with the applicable building code.

5. Change Section 2310.2.3 to read:

(N)2310.2.3 Heating equipment. Heating equipment installed in Class I, II or IIIA liquid storage or dispensing areas shall be maintained in accordance with the applicable building code.

6. Change Section 2310.2.3.3 to read:

(N)2310.3.3 Hoses and nozzles. Hoses and nozzles shall be maintained in accordance with the applicable building code.

7. Change Section 2310.3.5 to read:

(N)2310.3.5 Liquefied petroleum gas. Liquefied petroleum gas cylinders shall not be filled at marine motor fuel-dispensing facilities unless approved.

8. Change Section 2310.6 to read:

(N)2310.6 Fire protection. Fire protection features for marine motor fuel-dispensing facilities shall be maintained in accordance with the applicable building code.

J. The following changes shall be made to Section 2311, Repair Garages:

1. Change Section 2311.1 to read:

2311.1 General. Operation and maintenance of repair garages shall comply be in accordance with this section and other applicable provisions of this code. Repair garages for vehicles that use more than one type of fuel shall comply with the applicable provisions of this section for each type of fuel used.

Where a repair garage includes a motor fuel-dispensing facility, the fuel-dispensing operation shall comply with the requirements of this chapter for motor fuel-dispensing facilities.

2. Change Section 2311.2 to read:

(N)2311.2 Storage and use of flammable and combustible liquids. The storage and use of flammable and combustible liquids in repair garages shall maintained in accordance with the applicable building code.

3. Change Section 2311.2.3 to read:

(N)2311.2.3 Drainage and disposal of liquids and oil soaked waste. Contents of oil separators, traps and floor drainage systems shall be collected at sufficiently frequent intervals and removed from the premises to prevent oil from being carried into the sewers.

4. Change Section 2311.3.1 to read:

(N)2311.3.1 Equipment. Appliances and equipment installed in a repair garage shall be maintained in accordance with the applicable building code.

5. Change Section 2311.4 to read:

(N)2311.4 Below-grade areas. Pits and below-grade work areas in repair garages shall be maintained in accordance with the applicable building code.

6. Delete Section 2311.4.1.

7. Change Section 2311.4.2 to read:

(N)2311.4.2 Means of egress. Means of egress for pits and below-grade work areas shall be maintained in accordance with the applicable building code.

8. Change Section 2311.4.3 to read:

(N)2311.4.3 Ventilation. Where Class I liquids or LP-gas are stored or used within a building having a basement or pit wherein flammable vapors could accumulate, the basement or pit mechanical ventilation, where provided, shall be maintained in accordance with the applicable building code.

9. Change Section 2311.7.1 to read:

(N)2311.7.1 Ventilation. Ventilation required for repair garages used for the repair of natural gas-fueled vehicles or hydrogen-fueled vehicles shall be maintained in accordance with the applicable building code.

Exception: Repair garages with natural ventilation when approved.

10. Delete Section 2311.7.1.1.

11. Change Section 2311.7.1.2 to read:

(N)2311.7.1.2 Operation. The mechanical ventilation system shall be maintained in accordance with the applicable building code.

12. Change Section 2311.7.2 to read:

(N)2311.7.2 Gas detection system. Gas detection systems required for repair garages used for repair of vehicles fueled by nonodorized gases, including hydrogen and nonodorized liquefied natural gas, shall be maintained in accordance with the applicable building code.

13. Delete Section 2311.7.2.1.

14. Delete Section 2311.7.2.1.1.

15. Delete Section 2311.7.2.2.

16. Delete Section 2311.7.2.3.

Statutory Authority

§ 27-97 of the Code of Virginia.

Historical Notes

Derived from Volume 13, Issue 12, eff. April 15, 1997; amended, Virginia Register Volume 19, Issue 25, eff. October 1, 2003; Volume 27, Issue 02, eff. March 1, 2011; Change in Effective Date, 27:5 VA.R. 533 November 8, 2010; amended, Virginia Register Volume 30, Issue 16, eff. July 14, 2014; Volume 34, Issue 18, eff. October 16, 2018.

Website addresses provided in the Virginia Administrative Code to documents incorporated by reference are for the reader's convenience only, may not necessarily be active or current, and should not be relied upon. To ensure the information incorporated by reference is accurate, the reader is encouraged to use the source document described in the regulation.

As a service to the public, the Virginia Administrative Code is provided online by the Virginia General Assembly. We are unable to answer legal questions or respond to requests for legal advice, including application of law to specific fact. To understand and protect your legal rights, you should consult an attorney.